26523

ACIC 300V, 2 Tri #18 Str TC, PVC Ins E1, IS/OS, PVC Jkt, SIA Armor, Blk PVC Jkt, 105C Dry 75C Wet CSA HLBCD SUN RES -40C

26523
Canadian Instrumentation Cable TC-ACIC 300V, 2 Triad 18AWG (7x26) Tinned Copper, PVC Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, PVC Inner Jacket, Steel Interlock Armor, Black PVC Outer Jacket, 105C Dry 75C Wet CSA HLBCD SUN RES -40C
Get Product Alerts
Specifications

Put-Up Type

Reel

Product Overview

Suitable Applications

Instrumentation

Construction Details
Conductor
Element Number of Element Size Stranding Material
Conductor(s) 3 18 AWG 7x26 TC - Tinned Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) PVC - Polyvinyl Chloride 0.025 in (0.64 mm) 0.096 in (2.4 mm) Red, Black, White
Inner Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 20 AWG (7x28) TC
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 18 AWG (7x26) TC
Inner Jacket
Separator Material Nom. Thickness Nom. Diameter Ripcord
Polyester Tape PVC - Polyvinyl Chloride 0.047 in (1.2 mm) 0.507 in (12.9 mm) Yes
Armor
Armor Type & Material Armor Thickness Armor Material Diameter
SIA - Steel Interlock Armor 0.025 in (0.64 mm) 0.727 in (18.5 mm)
Outer Jacket
Material Nom. Thickness Nom. Diameter
PVC - Polyvinyl Chloride 0.052 in (1.3 mm) 0.831 in (21.1 mm)

Overall Cable Diameter (Nominal)

0.831 in (21.1 mm)

Electrical Characteristics
Electricals
Element Nom. Conductor DCR Nom. Inner Shield DCR Max. Current
Triad(s) 7.4 Ohm/1000ft 7.06 Ohm/km (2.15 Ohm/1000ft) 9.1 Amps per Conductor at 30ºC
Voltage
Voltage Rating
300 V (ACIC)
Mechanical Characteristics
Temperature
Operating
-40°C To +75°C Wet, -40°C To +105°C Dry
Bend Radius
Stationary Min. Installation Min.
9.97 in (253 mm) 9.97 in (253 mm)

Max. Pull Tension

369.4 lbs (167.6 kg)

Bulk Cable Weight

452 lbs/1000ft

Standards and Compliance

Environmental Suitability

Indoor/Outdoor, Indoor, Outdoor, Sunlight Resistance, UV Resistance

Flammability / Reaction to Fire

FT4

CEC / C(UL) Compliance

HL, ACIC

History

Update and Revision

Revision Number: 0.85 Revision Date: 06-30-2022