9412

High Perform Instr, 1 Pr #12 Str TC, PVC Ins E2, PVC Jkt, PLTC-ER

9412
High Performance Instrumentation, 1 Pair 12AWG (65x30) Tinned Copper, PVC Insulation E2 Color Code, PVC Outer Jacket, PLTC-ER
Request Sample Get Product Alerts
Specifications
Product Overview

Suitable Applications

Instrumentation, Sensors, Valves, Positioners, 4-20mA, 0-10V

Construction Details
Conductor
Element Number of Element Size Stranding Material
Pair(s) 1 12 AWG 65x30 TC - Tinned Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Pair(s) PVC - Polyvinyl Chloride 0.025 in (0.64 mm) 0.143 in (3.63 mm) Black, Red
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC - Polyvinyl Chloride 0.042 in (1.1 mm) 0.370 in (9.40 mm) Yes

Overall Cable Diameter (Nominal)

0.370 in (9.40 mm)

Electrical Characteristics
Electricals
Element Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Max. Current
Pair(s) 1.8 Ohm/1000ft (5.9 Ohm/km) 25 pF/ft (82 pF/m) 17 Amps per Conductor at 25ºC
Voltage
UL Voltage Rating
300 V (PLTC), 150 V (ITC)
Mechanical Characteristics
Temperature
UL Temperature Operating
105°C -30°C to +105°C

Table Notes

AWM 80°C

Bend Radius
Stationary Min. Installation Min.
3.7 in (94 mm) 3.7 in (94 mm)

Max. Pull Tension

169 lbs (76.7 kg)

Bulk Cable Weight

77 lbs/1000ft

Standards and Compliance

Environmental Suitability

Indoor/Outdoor, Sunlight Resistance

Flammability / Reaction to Fire

UL1685 UL Loading, T-29-520, IEEE 1202, FT4

NEC / UL Compliance

Article 725, Article 727, CL3R, ITC-ER, PLTC-ER

AWM Compliance

AWM 2464

European Directive Compliance

EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)

APAC Compliance

China RoHS II (GB/T 26572-2011)

History

Update and Revision

Revision Number: 0.381 Revision Date: 04-08-2022

Part Numbers
Item # Color UPC
9412 0601000 Chrome 612825240297
9412 0602500 Chrome 612825240303
9412 060500 Chrome 612825240310