3079A

Profibus, 1 Pr #22 Sol BC, PE Ins, OS+TC Brd, PVC Jkt, PLTC CMG Profibus DP

...
Profibus, 1 Pair 22AWG (Solid) Bare Copper, PE Insulation, Overall Beldfoil®+Tinned Copper Braid(65%) Shield, PVC Outer Jacket, PLTC CMG AWM 20201 SUN RES Profibus DP
Request Sample Get Product Alerts
Specifications
Product Overview

Suitable Applications

harsh environment, outdoors, data transmission applications such as Profibus DP or PA, Instrumentation and computer cable, etc. exposure to temperature extremes, humidity/moisture, dust, and oil.

Construction Details
Conductor
Element Number of Element AWG Stranding Material
Pair(s) 1 22 Solid BC - Bare Copper
Insulation
Element Material Thickness Color Code Notes
Pair(s) PE - Polyethylene (Foam) 0.035 in Red & Green Flame Retardant, Foam w/ skin
Outer Shield Material
Shield Type Material Coverage
Tape + Braid Bi-Laminate (Alum+Poly) + Tinned Copper (TC) 100% + 65%
Outer Jacket Material
Material Thickness Nom. Diameter
PVC - Polyvinyl Chloride 0.043 in 0.315 in

Cable Diameter (Nominal)

0.315 in

Electrical Characteristics
Electricals
Element Nom. Conductor DCR Characteristic Impedence Nom. Velocity of Prop. Max. Current
Pair(s) 16 Ohm/1000ft 150 Ohm 78% 2.3 Amps per Conductor

Nom. Outer Shield DCR

3.9 Ohm/1000ft

High Frequency (Nominal/Typical)
Element Frequency [MHz] Nom. Insertion Loss
Pair(s) 0.2 MHz 0.27 dB/100ft
4 MHz 0.67 dB/100ft
16 MHz 1.37 dB/100ft
High Freq
Frequency [MHz] Max. Insertion Loss (Attenuation)
0.2 MHz 1.1 dB/100m
4 MHz 2.65 dB/100m
16 MHz 5.4 dB/100m
Voltage
UL Voltage Rating
300 V (CMG, PLTC), 600 V (UL AWM 20201)
Mechanical Characteristics
Temperature
UL Rating Operating
75°C (UL AWM 20201) -30°C to +75°C
Bend Radius
Stationary Min. Installation Min.
3.2 in 2.4 in

Max. Pull Tension

50 lbs

Bulk Cable Weight

52 lbs/1000ft

Standards and Compliance

Environmental Suitability

Indoor, Sunlight Resistance

Flammability / Fire Resistance

UL1685 FT4 Loading, FT4, 1202, IEC 60332-1-2

NEC / UL Compliance

Article 725, Article 800, CMG, PLTC

AWM Compliance

20201

CEC / C(UL) Compliance

CMG

CPR Euroclass

Eca

European Directive Compliance

EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)

Product Notes

Notes

Siemens Sinec L2 Cable. For CPE jacketed version order Part No. YR45047. For LSZH (FRNC) jacketed version, order Part No. 3079T or YR44731.

History

Update and Revision

Revision Number: 0.398 Revision Date: 07-02-2021