29501F

VFD 300% Gnd, 3C+G #14 Str TC, XLPE Ins+PVC Gnd, OS+TC Brd w/#14 TC Drain, Blk TPE Jkt, 600/1000V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC

...
Belden 300% Ground Extra Flexible VFD, 3 Conductor 14AWG (104x30) Tinned Copper, XLPE Insulation M4 Color Code+PVC Insulated Ground, Overall Beldfoil®+Tinned Copper Braid(85%) Shield w/14AWG Tinned Copper Drain, Black TPE Outer Jacket, 600/1000V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable 1000V WTTC 600V CIC TC SUN RES OIL RES II DIR BUR
Request Sample Get Product Alerts

Specifications

Put-Up Type

Reel

Product Overview

Suitable Applications

Variable Frequency Drives (VFD); AC Motor and Drive Systems, Exposure to high flex, motion, and abrasion, Hard to reach installation areas

Construction Details
Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 3 14 AWG 104x34 TC - Tinned Copper
Ground Wire 1 14 AWG 104x34 TC - Tinned Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) XLPO - Crosslink Polyolefin 0.046 in (1.2 mm) 0.167 in (4.24 mm) ICEA Chart M4
Ground Wire PVC - Polyvinyl Chloride 0.046 in (1.2 mm) 0.167 in (4.24 mm) Green/Yellow Stripe
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Tri-Laminate (Alum+Poly+Alum) 100% 14 AWG (104x34) TC
Braid Tinned Copper (TC) 86%
Outer Jacket
Separator Material Nom. Thickness Nom. Diameter Ripcord
Polyester Tape TPE - Thermoplastic Elastomer 0.073 in (1.9 mm) 0.587 in (14.9 mm) Yes

Overall Cable Diameter (Nominal)

0.587 in (14.9 mm)

Electrical Characteristics
Electricals
Element Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Other (Conds + Shield) Nom. Characteristic Impedence Nom. Velocity of Prop. Max. Current
Conductor(s) 2.468 Ohm/1000ft 40 pF/ft (130 pF/m) 72 pF/ft (240 pF/m) 46 Ohm 55% 25 Amps per Conductor at 30ºC (per NEC)
2.73 Ohm/1000ft (8.96 Ohm/km) 25 Amps per Conductor at 30ºC (per NEC)
Voltage
UL Voltage Rating
1000 V (TC-ER, XHHW-2, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC)
Mechanical Characteristics
Temperature
UL Temperature Operating
90°C Dry, 90°C Wet -40°C To +90°C
Bend Radius
Stationary Min. Installation Min.
7.0 in (180 mm) 7.0 in (180 mm)

Max. Pull Tension

340 lbs (150 kg)

Bulk Cable Weight

216 lbs/1000ft

Standards and Compliance

Environmental Suitability

Indoor, Outdoor, Sunlight Resistance

Sustainability

CA Prop 65

Flammability / Reaction to Fire

UL 1685 UL Loading, FT4, IEEE 1202 FT4

NEC / UL Compliance

Article 336, Article 310, TC-ER, XHHW-2, UL Flexible Motor Supply Cable

CEC / C(UL) Compliance

CIC, TC

ICEA Compliance

S-95-658

European Directive Compliance

EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)

APAC Compliance

China RoHS II (GB/T 26572-2011)

History

Update and Revision

Revision Number: 0.191 Revision Date: 12-22-2023

Part Numbers
Item # Color Putup Type Length UPC
29501F 0101000 Black Reel 1,000 ft 612825367222
29501F 0105000 Black Reel 5,000 ft 612825367253