3037A

300V, (16 triad) 18 AWG (7x26) BC, (1) 22 AWG (7x30) BC, PVC/PVC, IS/OS, PLTC-ER, CMG

...
Sixteen 18 AWG traids stranded (7x26) bare copper conductors, one 22 AWG stranded (7x30) bare copper conductor, twisted pairs, PVC insulation, Individual and overall Beldfoil® shield (100% coverage), PVC jacket.
Request Sample Get Product Alerts
Specifications
Physical Characteristics (Overall)
Conductor
AWG Stranding Material No. of Triads
18 7x26 BC - Bare Copper 16
22 7x30 BC - Bare Copper

Conductor Count

49

Insulation
Material Nominal Wall Thickness
PVC - Polyvinyl Chloride 0.014 in
Color Chart
Number Color
1 Black and White and Red and Numbered 1
2 Black and White and Red and Numbered 2
3 Black and White and Red and Numbered 3
4 Black and White and Red and Numbered 4
5 Black and White and Red and Numbered 5
6 Black and White and Red and Numbered 6
7 Black and White and Red and Numbered 7
8 Black and White and Red and Numbered 8
9 Black and White and Red and Numbered 9
10 Black and White and Red and Numbered 10
11 Black and White and Red and Numbered 11
12 Black and White and Red and Numbered 12
13 Black and White and Red and Numbered 13
14 Black and White and Red and Numbered 14
15 Black and White and Red and Numbered 15
16 Black and White and Red and Numbered 16
17 Orange
Color Chart 2
Number Color
1 Black & White & Red and Numbered 1
2 Black & White & Red and Numbered 2
3 Black & White & Red and Numbered 3
4 Black & White & Red and Numbered 4
5 Black & White & Red and Numbered 5
6 Black & White & Red and Numbered 6
7 Black & White & Red and Numbered 7
8 Black & White & Red and Numbered 8
9 Black & White & Red and Numbered 9
10 Black & White & Red and Numbered 10
11 Black & White & Red and Numbered 11
12 Black & White & Red and Numbered 12
13 Black & White & Red and Numbered 13
14 Black & White & Red and Numbered 14
15 Black & White & Red and Numbered 15
16 Black & White & Red and Numbered 16
Communication Wire Orange
Inner Shield
Type Material Material Trade Name Coverage [%] Drainwire Material Drainwire AWG Drainwire Construction n x D
Tape Bi-Laminate (Alum+Poly) Beldfoil® 100% TC - Tinned Copper 20 7x28
Outer Shield
Type Material Material Trade Name Coverage [%] Drainwire Material Drainwire AWG Drainwire Construction n x D
Tape Bi-Laminate (Alum+Poly) Beldfoil® 100% TC - Tinned Copper 18 7x26
Outer Jacket
Material Nominal Diameter Nominal Wall Thickness Ripcord
PVC - Polyvinyl Chloride 0.903 in 0.073 in Yes
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR Nominal Inner Shield DCR Nominal Outer Shield DCR
5.86 Ohm/1000ft 10.3 Ohm/1000ft 6 Ohm/1000ft
Voltage
UL Voltage Rating
300 V RMS
Temperature Range

UL Temp Rating

105°C

Operating Temp Range

-30°C To +105°C

Mechanical Characteristics

Bulk Cable Weight

572 lbs/1000ft

Max. Pull Tension

831 lbs

Min. Bend Radius/Minor Axis

10.5 in

Standards

NEC Articles

Article 800

NEC/(UL) Compliance

CMG, ITC, PLTC

CEC/C(UL) Compliance

CMG

UL AWM Style Compliance

AWM 2464

Applicable Environmental and Other Programs

EU Directive 2000/53/EC (ELV)

Yes

EU Directive 2011/65/EU (RoHS 2)

Yes

EU Directive 2012/19/EU (WEEE)

Yes

EU Directive 2015/863/EU (RoHS 2 amendment)

Yes

EU Directive Compliance

EU Directive 2003/11/EC (BFR)

MII Order #39 (China RoHS)

Yes

Suitability

Suitability - Burial

Yes

Suitability - Sunlight Resistance

Yes

Flammability, LS0H, Toxicity Testing

UL Flammability

UL1685 UL Loading

CSA Flammability

FT4

ICEA Flammability

T-29-520

IEEE Flammability

1202

UL voltage rating

300 V RMS

Plenum/Non-Plenum

Plenum (Y/N)

No

History

Update and Revision

Revision Number: 0.184 Revision Date: 04-08-2022