8724

Audio, Control and Instrumentation, 1 Pr+2 C 22 AWG Stranded, Shielded/Unshielded, CM

...
1 Pair+2 Conductors 22 AWG stranded (7x30) tinned copper conductors, polypropylene insulation, one pair Beldfoil® shielded (100% coverage), stranded tinned copper drain wire, CM PVC jacket.
Get Product Alerts
Specifications
Product Overview

Suitable Applications

low voltage analog signals (4-20ma, 0-10v, ...); low voltage digital control (24v, …); line level audio; computer communication; panel wiring

Construction Details
Conductor
Element Number of Element Size Stranding Material
Conductor(s) 2 22 AWG 7x30 TC - Tinned Copper
Conductor(s) 2 22 AWG 7x30 TC - Tinned Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) PP - Polypropylene 0.0085 in (0.22 mm) 0.046 in (1.2 mm) Black, Red
Conductor(s) PP - Polypropylene 0.0085 in (0.22 mm) 0.046 in (1.2 mm) Green, White
Inner Shield
Element Shield Type Material Coverage Drainwire Type
Pair(s) Tape Bi-Laminate (Alum+Poly) 100% 24 AWG (7x32) TC
Conductor(s) No Shield
Outer Shield
Material
No Shield
Outer Jacket
Material Nom. Thickness Nom. Diameter
PVC - Polyvinyl Chloride 0.019 in (0.48 mm) 0.165 in

Overall Cable Diameter (Nominal)

0.165 in.

Electrical Characteristics
Electricals
Element Nom. Conductor DCR Nom. Inner Shield DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Other (Conds + Shield) Nom. Characteristic Impedence Nom. Velocity of Prop. Max. Current
Conductor(s) 15 Ohm/1000ft 34 pF/ft (110 pF/m) 67 pF/ft (220 pF/m) 48 Ohm 66% 2.9 Amps per Conductor at 25ºC
Conductor(s) 15 Ohm/1000ft (49 Ohm/km) 15.76 Ohm/1000ft (51.71 Ohm/km) 2.9 Amps per Conductor at 25ºC
Voltage
UL Voltage Rating
300 V
Mechanical Characteristics
Temperature
UL Temperature Operating
90°C -30°C To +90°C
Bend Radius
Stationary Min. Installation Min.
1.65 in (41.9 mm) 1.65 in

Max. Pull Tension

41 lbs (19 kg)

Bulk Cable Weight

20 lbs/1000ft

Standards and Compliance

Environmental Suitability

Indoor (Not Riser or Plenum), Indoor, Sunlight Resistance

Flammability / Reaction to Fire

UL 1685 UL Loading

NEC / UL Compliance

Article 800, CM

CEC / C(UL) Compliance

CM

European Directive Compliance

EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)

APAC Compliance

China RoHS II (GB/T 26572-2011)

History

Update and Revision

Revision Number: 0.458 Revision Date: 01-20-2023

Part Numbers
Item # Color Putup Type Length UPC
8724 0601000 Chrome Reel 1,000 ft 612825214601
8724 060U1000 Chrome UnReel 1,000 ft 612825427438
8724 060Z1000 Chrome ReelTuff Box 1,000 ft 612825214618
8724 0605000 Chrome Reel 5,000 ft 612825214588
Resources
All Resources
Compliance Documentation