8788

Audio, Control and Instrumentation, 5 Conductor 22 AWG (3C Indiv. Shielded Quads; 2C Unshielded), CM

...
22 AWG stranded (7x30) TC conductors, PVC insulation, (2) conductors unshielded, (3) conductors cabled and separately Beldfoil® Shielded (100% Coverage) with TCB solid 29 AWG drain wires, PVC jacket.
Get Product Alerts
Specifications
Product Overview

Suitable Applications

low voltage analog signals (4-20ma, 0-10v, ...); low voltage digital control (24v, …); line level audio; computer communication; panel wiring

Physical Characteristics (Overall)
Conductor
AWG Stranding Material No. of Conductors
22 7x30 TC - Tinned Copper 3
22 TC - Tinned Copper 2

Conductor Count

5

Insulation
Material
PVC - Polyvinyl Chloride
PVC - Polyvinyl Chloride
Color Chart
Number Color
1 Black (shielded)
2 Red (shielded)
3 Green (shielded)
4
5
Color Chart 2
Color
Yellow
Blue
Inner Shield Material
Type Material Material Trade Name Coverage [%] Drainwire Material Drainwire AWG Drainwire Construction n x D
Tape Bi-Laminate (Alum+Poly) Beldfoil® 100% TCB - Tinned Cadmium Bronze 29 Solid
No Shield 100%

Table Notes

Non-hygroscopic Filler

Outer Shield Material
Material
No Shield
Outer Jacket Material
Material Nominal Diameter
PVC - Polyvinyl Chloride 0.236 in
Construction and Dimensions
Cabling
Filler
Non-hygroscopic Inner Shield Filling Compound
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR Nominal Inner Shield DCR
15 Ohm/1000ft 38 Ohm/1000ft
Capacitance
Nom. Capacitance Conductor to Conductor
34 pF/ft
Current
Max. Recommended Current [A]
2.1 Amps per Conductor at 25ºC
Voltage
UL Voltage Rating
300 V RMS

Electrical Characteristics Notes

Nom. Capacitance Shield to Shield: 125 pF/ft

Temperature Range

Non-UL Temp Rating

60°C

Operating Temp Range

-20°C To +60°C

Mechanical Characteristics

Bulk Cable Weight

31 lbs/1000ft

Max. Pull Tension

45.5 lbs

Min Bend Radius/Minor Axis

2.5 in

Standards

NEC/(UL) Compliance

CM

Applicable Environmental and Other Programs

Environmental Space

Indoor (Not Riser or Plenum)

EU Directive Compliance

EU Directive 2011/65/EU (ROHS II)

EU CE Mark

Yes

Suitability

Suitability - Indoor

Yes

Flammability, LS0H, Toxicity Testing

UL Flammability

UL1685 UL Loading, VW-1

UL voltage rating

300 V RMS

Product Notes

Notes

(2) Unshielded conductors cabled around a non-hygroscopic filler. Drain wire for each conductor is tinned cadmium bronze ribbon under 100% Beldfoil« shield coverage.

History

Update and Revision

Revision Number: 0.271 Revision Date: 03-16-2021

Part Numbers
Item # Color Putup Type Length UPC
8788 060500 Chrome Reel 500 ft 612825216445